DW-RTD
Screw-In RTD and Thermocouple Temperature Sensor, Pt100 or Pt1000, Optional 4–20mA
Head-type screw-in temperature sensor with a Pt100 or Pt1000 RTD or a thermocouple, an optional 4–20 mA head-mounted transmitter, a 304 or 316L stainless steel probe of 20 to 1000 mm and threaded, clamp or flange connections, for liquids and gases in pipes and vessels.
- Sensing element
- Pt100, Pt1000 or thermocouple
- Output
- RTD/TC direct or 4–20 mA
- Temperature range
- −50 to +250 °C
Features
- Pt100 or Pt1000 RTD (dual Pt100 optional), or thermocouple types B, E, J, K, N, R, S and T
- Optional head-mounted 4–20 mA two-wire transmitter
- Mineral-insulated measuring insert: quick response, bendable, vibration resistant
- Reliable sealing under vacuum and overpressure
- Probe Ø4, 6 or 8 mm and 20 to 1000 mm long, in 304 or 316L stainless steel
- Aluminium terminal head with M20×1.5 cable gland, IP65
Typical applications
Full specifications
PDF DW-RTD Datasheet| Performance | |
|---|---|
| Sensing element | Pt100 / Pt1000 / Cu50 RTD (dual Pt100 optional); thermocouple type B, E, J, K, N, R, S or T |
| Temperature range | −50 to +250 °C (standard screw-in probe) |
| Accuracy | Class A: ±(0.15 + 0.002|t|) °C; Class B: ±(0.3 + 0.005|t|) °C (IEC 751) |
| Pt100 R(100 °C)/R(0 °C) | 1.3851 |
| Measuring current | < 2 mA |
| Output | |
| Output signal | RTD or thermocouple direct, or 4–20 mA two-wire via head-mounted transmitter |
| Electrical | |
| Supply voltage | 12–40 V DC (with transmitter) |
| Load resistance | RL ≤ (U − 12) / 0.021 Ω (transmitter) |
| Response time | 90% of final value in 1 s (transmitter) |
| Temperature drift | 0.02% FS/°C (standard); 0.0075% FS/°C (isolated) (transmitter) |
| Wiring | 2-wire or 3-wire RTD connection |
| Mechanical | |
| Process connection | M20×1.5, M27×2, M14×1.5, G1/4, G1/2, G3/4, NPT1/4, NPT1/2, NPT3/4, G1/2 sleeve, 2" clamp, others |
| Installation method | Flange, clamp, direct insertion or screw base |
| Probe diameter | Ø4, Ø6 or Ø8 mm; Ø8–Ø16 mm with detachable sleeve; others |
| Probe length | 20 to 1000 mm, others on request |
| Material | 304 or 316L stainless steel (probe and connection) |
| Terminal head | Aluminium alloy, M20×1.5 cable gland, IP65 |
| Cold-end length | 0, 50 or 100 mm, or to order |
| Environmental | |
| Ambient temperature | −40 to +80 °C (transmitter) |
| Storage temperature | −40 to +100 °C (transmitter) |
| Vibration resistance | 4 g, 2–150 Hz (transmitter) |
Questions about the DW-RTD
How accurate is the DW-RTD?
The DW-RTD (Screw-In RTD and Thermocouple Temperature Sensor) is specified with an accuracy of Class A: ±(0.15 + 0.002|t|) °C; Class B: ±(0.3 + 0.005|t|) °C (IEC 751).
What output signal or interface does the DW-RTD use?
The output of the DW-RTD (Screw-In RTD and Thermocouple Temperature Sensor) is RTD/TC direct or 4–20 mA.
What supply voltage does the DW-RTD need?
The DW-RTD (Screw-In RTD and Thermocouple Temperature Sensor) is powered by 12–40 V DC (with transmitter).
What is the sensing element of the DW-RTD?
The DW-RTD (Screw-In RTD and Thermocouple Temperature Sensor) is specified with a sensing element of Pt100, Pt1000 or thermocouple.
What is the DW-RTD used for?
The DW-RTD (Screw-In RTD and Thermocouple Temperature Sensor) is typically used for air conditioning and refrigeration, HVAC, apparatus engineering, and liquids and gases in process pipes and vessels.
Where can I get the DW-RTD datasheet?
The DW-RTD datasheet is a free PDF on this page, with the full specification table. For drawings in CAD format or a custom version, contact DWIN sales.
Does DWIN offer OEM or custom versions of the DW-RTD?
Yes. DWIN adapts the DW-RTD from its existing design: housing and mounting, cable and connector, interface and protocol, firmware and range. Engineering confirms feasibility, then DWIN builds samples for your tests before series production.
How do I get a quote or samples of the DW-RTD?
Use the quote form on this page or email xyx@gzdwin.com with the DW-RTD, your quantity, application and destination country. DWIN sales replies with pricing, lead time and sample availability.