Cost-effective digital level transmitter with a silicon resistance sensor and RS485 MODBUS output, in ranges from 3.5m to 350m H2O with ±0.5%F.S accuracy.

Range
3.5m / 10.5m
Protection
IP68
Supply voltage
4.5–30VDC / 3–4.1VDC

Features

  • Silicon resistance sensor
  • RS485 bus and MODBUS protocol
  • Wide supply: 4.5–30VDC or 3–4.1VDC
  • Gage, absolute or sealed gage type
  • Over voltage and reverse protected

Typical applications

  • River and lake level measurement
  • Deep well and groundwater monitoring
  • Sewage and storm-water basin monitoring
  • Sewer lift and pumping stations

Full specifications

PDF CS-PT482 Datasheet EN
CS-PT482 specifications as published. Values are typical unless stated.
Performance specifications
Reference conditionsTemperature 25°C, power 12VDC, RH 45%~75%, atmospheric pressure 86KPa~106KPa
Standard range (H2O) / proof (H2O), range 13.5m / 10.5m
Standard range (H2O) / proof (H2O), range 27.0m / 21m
Standard range (H2O) / proof (H2O), range 310m / 30m
Standard range (H2O) / proof (H2O), range 420m / 60m
Standard range (H2O) / proof (H2O), range 540m / 120m
Standard range (H2O) / proof (H2O), range 660m / 120m
Standard range (H2O) / proof (H2O), range 7100m / 200m
Standard range (H2O) / proof (H2O), range 8200m / 400m
Standard range (H2O) / proof (H2O), range 9350m / 700m
Pressure typeDefault Gage (G), Absolute (A) or Seal Gage (S) optional
Accuracy at 25°C±0.5%F.S (include linearity, hysteresis, repeatability)
Long-term stability±0.25%FS/year
Response time≤10ms
Electrical
Output signalRS485 Bus and MODBUS Protocol
Supply voltage4.5–30VDC / 3–4.1VDC
Over voltage32VDC / 7VDC
Reverse voltage-32VDC / -7VDC
Supply current10mA / 7mA
Insulate resistance≥100MΩ@50VDC
Environmental
Operating temperature-20°C~60°C
Compensated temperature0°C~50°C
Storage temperature-40°C~85°C
Random vibration10g, 5–2000Hz
ShockX/Y/Z, 20g, sine 11ms
Drop (any axis)1m
Mechanical
Waterproof ratingIP68
Housing material304 stainless steel default, 316L stainless steel and Titanium optional
Seal materialNBR O-Ring default, FKM optional
Cable materialPE default, PUR and FEP optional
Notes
Note 1Range scaling is as small as 3/5 of the basic range and the minimum range is 3m H2O.
Note 2All intermediate range output transmitters (but pressure) are implemented with basic range expansion.

Dimensions and wiring

Drawing 1 for CS-PT482

Questions about the CS-PT482

What is the range of the CS-PT482?

The CS-PT482 digital level transmitter, silicon resistance, rs485 is specified with a range of 3.5m / 10.5m.

What is the protection of the CS-PT482?

The CS-PT482 digital level transmitter, silicon resistance, rs485 is specified with a protection of IP68.

What is the supply voltage of the CS-PT482?

The CS-PT482 digital level transmitter, silicon resistance, rs485 is specified with a supply voltage of 4.5–30VDC / 3–4.1VDC.

Where can I get the CS-PT482 datasheet?

The CS-PT482 datasheet is a free PDF on this page, with the full specification table. For drawings in CAD format or a custom version, contact DWIN sales.

Ask about the CS-PT482

Send your application, quantity and interface. We reply with pricing, lead time and sample availability.

Request a quote