CS-PT1350 CO2 Pressure Transmitter, Ceramic Cell, Copper Tube

CS-PT1350

CO2 Pressure Transmitter, Ceramic Cell, Copper Tube

Ceramic piezoresistive pressure transmitter for carbon dioxide units, 0–5…250bar gage, with 4–20mA output, ±1.0%F.S accuracy and IP66 protection.

Range
0–5…250bar (Gage)
Output
4–20mA
Protection
IP66
Supply voltage
8–36 VDC

Features

  • Φ6 x 60 copper process connection
  • Packard electrical connection
  • Brass shell
  • 8–36 VDC supply
  • Strong electromagnetic compatibility

Typical applications

  • Carbon dioxide units
  • Multi-line air conditioning
  • Precision computer room air conditioning
  • Air source heat pumps

Full specifications

PDF CS-PT1350 Datasheet EN
CS-PT1350 specifications as published. Values are typical unless stated.
Performance specifications
Reference conditionsTemperature: 20–25°C; Power supply: 12VDC; Relative humidity: 45%~75%; ambient atmospheric pressure: 86KPa~106KPa;
Pressure range0–5…250bar (Gage)
Overload pressure≥150%F.S
Burst pressure≥300%F.S
Accuracy at 25°C±1.0%F.S (include no-linearity, hysteresis, repeatability, and calibration error)
Long-term stability.±0.25%F.S/year
Response time(10%~90%)≤10ms
Medium temperature-30°C~115°C
Ambient temperature-35°C~105°C
Storage temperature-35°C~105°C
Output signal4–20mA
Supply voltage8–36 VDC
Output load≤ (U-8) / 0.023 Ω(Max: 600Ω)
Overvoltage36VDC
Reverse voltage-30VDC
Insulate resistance≥100MΩ@50VDC
IP ratingIP66
Random vibration10g, 5–2000Hz
ShockX/Y/Z, 20g, half-sine 11ms
Drop (any axis)1m
Pressure connectorΦ6 Copper pipes
Shell materialBrass

Dimensions and wiring

Drawing 1 for CS-PT1350

Questions about the CS-PT1350

What is the range of the CS-PT1350?

The CS-PT1350 co2 pressure transmitter, ceramic cell, copper tube is specified with a range of 0–5…250bar (Gage).

What is the output of the CS-PT1350?

The CS-PT1350 co2 pressure transmitter, ceramic cell, copper tube is specified with a output of 4–20mA.

What is the protection of the CS-PT1350?

The CS-PT1350 co2 pressure transmitter, ceramic cell, copper tube is specified with a protection of IP66.

Where can I get the CS-PT1350 datasheet?

The CS-PT1350 datasheet is a free PDF on this page, with the full specification table. For drawings in CAD format or a custom version, contact DWIN sales.

Ask about the CS-PT1350

Send your application, quantity and interface. We reply with pricing, lead time and sample availability.